Performance of high temperature heat pump for simultaneous and efficient production of ice water and process heat

Sammendrag

Industrial processes like milk production often require simultaneous cooling and heating at temperature of 1 °C to 10 °C and 90 °C to 120 °C, respectively. High temperature heat pumps (HTHP) with natural working fluids are a cost-, energy efficient and sustainable solution. In this work a 20 kWth lab scale cascade heat pump is analysed to predict the performance of a 300 kWth pilot plant. The test campaign covers an evaporation temperature range of -1 °C to +1 °C and a condenser temperature range of 113 °C to 118 °C enabling ice-water chilling from 10 °C to 4 °C and a hot-water heating from 85 °C to 116 °C A Combined heating and cooling COPcombined of 2.6 to 2.8 was achieved for a temperature lift of 110 K to 80 K, respectively. This performance gives a primary energy saving potential of 57% and a potential CO2-emission reduction of 94%. It can be concluded that HTHP can produce simultaneously chilled/ice-water and hot-process water efficiently for processes like drying, sterilization, pasteurization.
Les publikasjonen

Kategori

Vitenskapelig kapittel

Språk

Engelsk

Forfatter(e)

Institusjon(er)

  • SINTEF Energi AS / Gassteknologi
  • SINTEF Energi AS / Termisk energi
  • Norges teknisk-naturvitenskapelige universitet

År

2019

Forlag

International Institute of Refrigeration

Bok

Proceedings of the 25th IIR International Congress of Refrigeration. Montréal, Canada, August 24-30, 2019

ISBN

9782362150357

Side(r)

4632 - 4639

Vis denne publikasjonen hos Nasjonalt Vitenarkiv