Time to breakdown studies for liquids of different physico-chemical nature

Sammendrag

An automated setup for testing dielectric performance of liquids in a small point-to-plane gap is presented. It provides step voltages with rise times around 30 ns, with amplitudes up to 90 kV. Breakdown studies of thirteen different liquids were conducted with a gap distance of 4 mm in a test cell containing 20 ml liquid. The liquids were circulated and filtered after each breakdown to remove carbonized particles and relax space charges. Time to breakdown versus applied voltage was recorded, and for streamers that stopped mid gap, shadow graphic images of streamer structures were taken. Multivariate correlation studies between streamer properties and physio-chemical parameters of liquids were made, indicating relevance of liquid evaporation and electronic states of molecules.
Les publikasjonen

Kategori

Vitenskapelig Kapittel/Artikkel/Konferanseartikkel

Oppdragsgiver

  • Research Council of Norway (RCN) / 228850

Språk

Engelsk

Forfatter(e)

Institusjon(er)

  • SINTEF Energi AS / Elkraftteknologi
  • Sverige

År

2017

Forlag

IEEE conference proceedings

Bok

2017 IEEE 19th International Conference on Dielectric Liquids - ICDL

Hefte nr.

2017

ISBN

978-1-5090-4877-9

Vis denne publikasjonen hos Cristin