Til hovedinnhold
Norsk English

Air Flow Measurements During Medium-Voltage Load Current Interruptions

Sammendrag

Air has been considered a good alternative to SF6 as arc quenching medium for load break switchgear at medium voltage ratings. In this work, the air flow characteristics and influence from the electric arc have been studied for typical currents and over-pressures. The cooling air velocity is typically in the range 150 - 200 m/s and thus well below supersonic speed. The arc and the surrounding hot air severely affect the air flow pattern by causing clogging in the contact and nozzle region.
Les publikasjonen

Kategori

Vitenskapelig artikkel

Oppdragsgiver

  • Research Council of Norway (RCN) / 192918

Språk

Engelsk

Institusjon(er)

  • Norges teknisk-naturvitenskapelige universitet
  • SINTEF Energi AS / Elkraftteknologi

År

2015

Publisert i

Plasma Physics and Technology

ISSN

2336-2626

Årgang

2

Hefte nr.

1

Side(r)

83 - 87

Vis denne publikasjonen hos Cristin