To main content

Arc Voltage Distribution Measurement in Tube Constricted Ultrahigh-Pressure Nitrogen Arc

Arc Voltage Distribution Measurement in Tube Constricted Ultrahigh-Pressure Nitrogen Arc

Category
Academic chapter/article/Conference paper
Abstract
This work contributes to the fundamental understanding of axial voltage
distribution of the arc burning inside polytetrafluoroethylene (PTFE) tube at
very high filling pressures of nitrogen. The arc peak current of 85 A at a frequency
of 190 Hz with a fixed initial rate of rise of recovery voltage (IRRRV) of
approximately 50 V/μs is used throughout the study. Arc burning at three different
filling pressures are studied: 1 bar, 20 bar, and 40 bar. To examine the axial
voltage distribution in the arc, the arc voltage at three different axial position of
the arc is independently measured. For some cases, a 3 cubic centimeter heating
volume is attached to the ring electrode, which produces a back flow. For the
cases with a heating volume, the pressure rise in the heating volume is also measured.
It is observed that the pressure rise in the heating volume increases with the
filling pressure. In the presence of the heating volume at a high filling pressure
(i.e., 20 bar, 40 bar), the voltage drop increases significantly near the vent due to
the relatively cold gas flow.
Client
  • Research Council of Norway (RCN) / 280539
Language
English
Author(s)
Affiliation
  • Norwegian University of Science and Technology
  • SINTEF Energy Research / Elkraftteknologi
Year
2020
Publisher
Springer
Book
Proceedings of the 21st International Symposium on High Voltage Engineering
Issue
599
ISBN
978-3-030-31676-1
Page(s)
672 - 679