To main content

Modeling of Internal Pressure Dynamics in Mass-Impregnated Nondraining HVDC Cables

Abstract

Changing the current loading of mass-impregnated nondraining (MIND) power cables causes the pressure in the insulation to vary over a wide range. It is generally recognized that under certain conditions—typically after a large load reduction—the pressure becomes so low that shrinkage cavities (voids) form in the insulation and that partial discharges (PDs) may damage the insulation ignite. A finite-element model for temperature, electric field, and pressure dynamics throughout the insulation layer has been developed. Comparisons with previously obtained measurements on full-scale high voltage direct current (HVDC) subsea cable samples subjected to a variety of loading patterns, external pressures (sea depths), and ambient temperatures show that the model replicates the pressure behavior of the insulation reasonably well. Most importantly, the complicated viscoelastic properties of the lead sheath, which have a profound effect on the internal pressure dynamics and thereby on the prospects of forming potentially harmful cavities, appear to be sufficiently accurately modeled.
Read the publication

Category

Academic article

Language

English

Author(s)

Affiliation

  • SINTEF Energy Research / Elkraftteknologi

Year

2022

Published in

IEEE transactions on dielectrics and electrical insulation

ISSN

1070-9878

Volume

29

Issue

3

Page(s)

1135 - 1142

View this publication at Norwegian Research Information Repository