Parametric Stability Assessment of Single-Phase Grid-Tied VSCs Using Peak and Average DC Voltage Control

Abstract

A type of peak-value dc voltage control (denoted as PK control) was proposed in the literature for supporting the use of a smaller dc-side capacitance when the single-phase voltage source converter is operated as a static synchronous compensator. Although it was demonstrated to operate stably under several conditions, it will be revealed in this article how the PK control will suffer from a more severe small-signal stability issue under nonideal grid conditions than the conventional method of controlling the average value of the dc voltage (denoted as Avr control). Especially, it will be shown how the PK control is sensitive to some of the control parameters. To obtain these results, a parameter-oriented stability analysis method is developed in the linear time-periodic framework. Then, it is utilized for parametric stability assessments of the Avr and PK control. Finally, both frequency- and time-domain experimental results verified the effectiveness and accuracy of the applied method in the presented analysis.
Read the publication

Category

Academic article

Language

English

Author(s)

  • Zhang Chen
  • Takanori Isobe
  • Jon Are Wold Suul
  • Tomislav Dragicevic
  • Maria Marta Molinas Cabrera

Affiliation

  • SINTEF Energy Research / Energisystemer
  • Technical University of Denmark
  • Norwegian University of Science and Technology
  • University of Tsukuba

Year

2021

Published in

IEEE transactions on industrial electronics (1982. Print)

ISSN

0278-0046

Volume

69

Issue

3

Page(s)

2904 - 2915