Abstract
The rapid penetration of Inverter-Based Resources (IBRs) in modern power systems necessitates the deployment of Grid-Forming (GFM) converters to maintain grid stability, particularly under weak network conditions. Although full-order impedance models offer high-fidelity representations of converter dynamics, their dimensionality and numerical complexity obscure physical insight and create computational bottlenecks in large-scale studies. This paper develops a compact reduced-order closed-form impedance model for GFM converters with virtual-admittance control. The proposed reduction neglects the slow outer active- and reactive-power loops while preserving the inner-loop interactions governing harmonic-frequency dynamics. Explicit symbolic expressions for the converter terminal behavior are derived directly in the complex frequency domain. The analytical model is validated against the full-order numerical impedance model and frequency-scan simulations of a detailed nonlinear converter model. Finally, system-level stability assessments demonstrate that the proposed closed-form model accurately captures the dominant high-frequency dynamics required for reliable wideband harmonic stability analysis.