Abstract
Breakdown at triple junctions under AC stress often deviates from theoretical predictions. This work investigates whether surface charges from partial discharges (PDs) can explain the reduced breakdown strength compared to simulations. A typical geometry found in medium-voltage GIS systems was tested in a micro-gap configuration defined by assembly tolerances and with a 1.0 mm gap. Breakdown was measured by ramping the voltage while monitoring PD activity. The 1.0 mm gap, which produced minimal PDs, agreed well with simulations, whereas the micro-gap showed significant PD activity and correspondingly lower breakdown values. The reduction is attributed to surface charges acting as hetrocharges during polarity reversal, enhancing the electric field at the triple junction. Comparison with sinusoidal half-wave voltages confirmed that voltage magnitude alone cannot explain the behavior. The results highlight the importance of surface-charge dynamics in defining design criteria for geometries involving triple junctions.