To main content

Effect of Gas Composition on AC Breakdown Performance of C5-Fluoroketone/Air Mixture

Abstract

Arc-induced ageing of C5-fluoroketone (C5-FK)/air mixtures leads to C5-FK decomposition. This work aims to investigate the effect of reduced C5-FK content on AC breakdown performance and to examine whether arc-generated decomposition byproducts contribute to maintaining insulation strength. Progressive stress AC breakdown tests were performed in a 10 mm rod-plane gap at 1.3 bar for mixtures containing 7.5%, 6.5%, 5.5%, 4.5%, 2.5%, and 1% C5-FK in synthetic air. The results are compared with those from a previous investigation, in which a 7.5% C5-FK/air mixture was aged by free-burning arcs with a total energy equivalent to the estimated lifetime exposure of a medium-voltage load break switch. A monotonic decrease in AC breakdown voltage is observed with decreasing C5-FK concentration, indicating the strong influence of C5-FK content on power-frequency insulation performance. In contrast, the arc-aged mixture showed no reduction in AC breakdown voltage despite C5-FK decomposition. The results indicate that C5-FK depletion alone is not a reliable indicator of ageing effects in C5-FK/air mixtures. Arcing produces stable fluorocarbon byproducts, which may help mitigate the expected degradation in AC performance. The role of decomposition products must therefore be considered when evaluating long-term insulation performance of C5-FK-based systems.

Category

Academic chapter

Language

English

Author(s)

Affiliation

  • SINTEF Energy Research / Energy Technology
  • ETH Zurich
  • Norwegian University of Science and Technology

Year

2026

Publisher

IEEE (Institute of Electrical and Electronics Engineers)

Book

2026 IEEE International Conference on High Voltage Engineering and Application - ICHVE

ISBN

9798319501356

View this publication at Norwegian Research Information Repository