To main content

Empirical representation of transformer branch impedance frequency dependency

Abstract

High-frequency transformer models for use in system transient studies should include the transformer’s frequency-dependent effects to give reliable simulation results. The most accurate white-box modeling approach is based on the branch impedance matrix Zb with inclusion of frequency-dependent effects, in combination with the capacitance matrix. The required calculation of Zb at many time frequency samples using FEM can be very time consuming, due to the large dimension of Zb. We show that the frequency dependency in Zb can be approximately taken into account by an empirical frequency response that is derived from an eigenvalue of Zb from a representative transformer. That way, the long computation time by FEM is avoided. The proposed method is demonstrated to be more accurate than usage of the classical Fergestad’s damping factor method.
Read the publication

Category

Academic article

Language

English

Author(s)

Affiliation

  • SINTEF Energy Research / Energy Technology
  • Brazil
  • Uruguay

Year

2026

Published in

Electrical engineering (Berlin. Print)

ISSN

0948-7921

Volume

108

Issue

11

View this publication at Norwegian Research Information Repository