Abstract
The increasing concern on the use of synthetic fluids in heat pumps and refrigeration
applications have been increasing considerably over the last twenty years. Decarbonization of
the industrial and commercial sector via the use of natural working fluids is by far one of the
most effective measures to tackling global warming. However, this policy was also extended to
international organizations such as CERN (European Organization for Nuclear Energy) which
is highly energy intensive.
In 2008, detector cooling systems at CERN were based on single-phase pumped loop and oilfree
vapor compression cycle using perfluorocarbons (C6F14, C3F8). With the ongoing
advancement of silicon detector technologies, which demanded stringent mass minimization
within the detector volume, several alternative solutions were explored. CO2 was identified as
a radiation-hard coolant able to maximize the heat removal capability while minimizing the size
of hardware inside the detectors, feature extremely appreciated for low-mass detectors. The
developed CO2 system, named 2PACL (two-phase accumulator pumped loop) has proven to be
highly reliable and controllable. However, its efficiency, expressed as the ability of the coolant
to evacuate the heat generated by the sensor and adjacent electronics via an isothermal process,
deteriorates when approaching the low temperatures operation around -45°C. This reduction in
efficiency is primarily attributed to the decreased evaporating pressure at such temperatures. In
2018, the primary system responsible for transferring the heat from the 2PACL unit to the
external environment, was transitioned from HFC-based solution (R404A) to CO2. Since then,
CERN supports the development and implementation of green technologies as the only system
alternative to be used within the upgrades of the different subdetectors.
The future upgrade of the detectors under the HL-LHC program, which is necessary to increase
the amount of data and the foreseen collision rates, will require highly-effective and low mass
detector cooling down to temperatures around -80/-90 °C due to the higher radiation levels.
Superior performance given by high working pressure fluids is essential for the thermal
management of future detectors. To investigate new efficient coolants for the future domain of
operation, a sub-project was launched. In this respect, as first part of this thesis, a preliminary
study targeting natural working fluids points out krypton as a promising cooling agent.
Silicon detector trackers are expensive and fragile components demanding very harsh
requirement to the cooling system, mainly: high system’s stability to provide an accurate spatial
and temporal thermal stability along the entire detector structure, remote control due to the harmful
radioactivity level near the detectors, low mass contribution of the cooling system with
respect the overall mass installed around the detector. All these requirements, together with the
lack of any theoretical-experimental data on the use of krypton as refrigerant, pose a number of
challenges. To address those challenges, an innovative ejector-driven cooling system able to
cope with the demanding requirements of the detectors was designed, although the limited
project budget constrained both the development and the use of suitable components. The
comprehensive research program included the development of a test facility to study the
dynamic of the cycle starting from room temperature down to -80°C, with particular emphasis
on the system controllability and gradual cooldown of the detector. The setup allows for testing
the gas, supercritical and two-phase state of krypton while providing measurements of the
significant parameters necessary for tuning the numerical models used for sizing of the ejectors,
expansions devices and heat exchangers. All the different transient modes, comprising the
system startup, cooldown, supercritical and two-phase operation have both been modelled and
tested experimentally. Design guidelines were suggested accordingly to the future operating
range, mainly in terms of minimum operating temperature.