Initiation of vented water trees from the conductor screen of MV XLPE insulated cables

Sammendrag

It has previously been shown for service aged XLPE cables that porous structures in the conductor screen do develop and serve as paths for contaminants and corrosion products from the aluminum conductor initiating vented water trees. It was found that a prerequisite for the formation of such structures is the presence of liquid water at the interface between the conductor and conductor screen causing corrosion. The main objective with this work is to reproduce this phenomenon in the laboratory and to examine if porous zones can develop even without service stress (voltage/current).

Kategori

Vitenskapelig Kapittel/Artikkel/Konferanseartikkel

Språk

Engelsk

Forfatter(e)

Institusjon(er)

  • SINTEF Energi AS / Elkraftteknologi
  • Nexans Norway AS

År

2012

Forlag

IEEE conference proceedings

Bok

Conference Record of the 2012 IEEE International Symposium on Electrical Insulation

Hefte nr.

2012

ISBN

978-1-4673-0486-3

Side(r)

386 - 390

Vis denne publikasjonen hos Cristin