Variable Transmission Voltage for Loss Minimization in Long Offshore Wind Farm AC Export Cables

Sammendrag

Connection of offshore wind farms to shore requires the use of submarine cables. In the case of long HVAC connections, the capacitive charging currents limit the transfer capability and lead to high losses. This paper shows that the losses can be substantially reduced by continuously adjusting the cable operating voltage according to the instantaneous wind farm power production. Calculations for a 320 MW wind farm connected to shore via a 200 km cable at 220 kV nominal voltage shows that an annual loss reduction of 9% is achievable by simply using a ±15% tap changer voltage regulation on the two transformers. Allowing a larger voltage regulation range leads to further loss reduction (13% for 0.4-1.0 p.u. voltage range). If the windfarm has a low utilization factor, the loss reduction potential is demonstrated to be as high as 21%. The methodology can be applied without introducing new technology that needs to be developed or qualified.
Les publikasjonen

Kategori

Vitenskapelig artikkel

Oppdragsgiver

  • Research Council of Norway (RCN) / 193823

Språk

Engelsk

Forfatter(e)

Institusjon(er)

  • SINTEF Energi AS / Energisystemer

År

2017

Publisert i

IEEE Transactions on Power Delivery

ISSN

0885-8977

Årgang

32

Hefte nr.

3

Side(r)

1422 - 1431

Vis denne publikasjonen hos Cristin