Experimental analysis of the r744 vapour compression rack equipped with the multi-ejector expansion work recovery module

Sammendrag

A test facility for the experimental investigation of the R744 vapour compression rack equipped with a multi-ejector expansion work recovery module was designed and manufactured. A comparison of the R744 multi-ejector refrigeration system with the R744 parallel compression system at the same test facility was carried out based on the energy performance characteristics of refrigeration capacity, power consumption, COP, and exergy efficiency. Apart from the system performance comparison, the influence of the pressure level in the flash tank on the system performance for the two alternatives was analysed. The experimental results indicate COP and exergy efficiency improvements of the multi-ejector refrigeration system up to 7% and 13.7%, respectively. The highest values of COP and exergy efficiency were obtained by a multi-ejector refrigeration system with the tank pressure lift close to the maximum value possible to operate the multi-ejector expansion module. The values of the effective compressor efficiencies were significantly different, depending on the operation module (cooling load and heat rejection conditions).

Kategori

Vitenskapelig artikkel

Oppdragsgiver

  • Research Council of Norway (RCN) / 196445

Språk

Engelsk

Forfatter(e)

Institusjon(er)

  • Politechnika Śląska
  • SINTEF Energi AS / Termisk energi
  • Norges teknisk-naturvitenskapelige universitet

År

2016

Publisert i

International journal of refrigeration

ISSN

0140-7007

Forlag

Elsevier

Årgang

64

Side(r)

93 - 107

Vis denne publikasjonen hos Cristin