Til hovedinnhold
Norsk English

Contact and nozzle wear from 100 interruptions for a puffer-type air load break switch

Sammendrag

One type test requirement for medium voltage load break switches is to interrupt 100
consecutive "mainly active loads". A puffer-type switch with axial-blown arc has been tested according
to the 630 A/24 kV ratings. The nozzle and contact wear were measured regularly to investigate design
requirements and the impact from nozzle wear on gas flow. The contact wear is only moderate, while
the nozzle wear causes a decrease in pressure build-up, which in turn may influence the interruption
performance.
Les publikasjonen

Kategori

Vitenskapelig artikkel

Oppdragsgiver

  • Research Council of Norway (RCN) / 235284

Språk

Engelsk

Institusjon(er)

  • SINTEF Energi AS / Elkraftteknologi

År

2017

Publisert i

Plasma Physics and Technology

ISSN

2336-2626

Årgang

4

Hefte nr.

1

Vis denne publikasjonen hos Cristin