Til hovedinnhold
Norsk English

Experimental investigation of a prototype R-600 compressor for high temperature heat pump

Sammendrag

This research experimentally investigates a prototype compressor in a high temperature heat pump for industrial waste heat recovery from 50 °C to heat delivery at 115 °C. Compressors are the limiting component in the development of high temperature heat pumps due to the high discharge pressure and temperature. The prototype compressor is tested with butane due to its favourable thermodynamic properties within the operating conditions. The compressor allows the heat pump to provide heating for industrial processes such as pasteurization, drying, sterilization and other processes which require high temperature heat. The heat pump will replace the heating capacities of low-pressure steam boilers. It will also provide cooling for industrial waste heat or other cooling demands, replacing cooling capacities from cooling towers. The experimental setup consists of a 20 kW heat pump designed with the flexibility for multiple operating conditions applicable to different industrial applications. The compressor is designed to enable suction and discharge temperatures up to 80 °C and 140 °C respectively. It is found to have a total compressor efficiency of 74% and a volumetric efficiency of 83%. The results showed good operating parameters (temperature, pressure) and the potential for even higher temperature heat delivery

Kategori

Vitenskapelig artikkel

Oppdragsgiver

  • Research Council of Norway (RCN) / 257632
  • Research Council of Norway (RCN) / 243679

Språk

Engelsk

Forfatter(e)

  • Opeyemi Olayinka Bamigbetan
  • Trygve Magne Eikevik
  • Petter Nekså
  • Michael Bantle
  • Christian Schlemminger

Institusjon(er)

  • Norges teknisk-naturvitenskapelige universitet
  • SINTEF Energi AS / Gassteknologi
  • SINTEF Energi AS / Termisk energi

År

2019

Publisert i

Energy

ISSN

0360-5442

Forlag

Elsevier

Årgang

169

Side(r)

730 - 738

Vis denne publikasjonen hos Cristin