Improving the pole relocating properties of vector fitting

Sammendrag

This paper describes a modification of the vector fitting (VF) procedure for rational function approximation of frequency-domain responses. The modification greatly improves the ability of VF to relocate poles to better positions, thereby improving its convergence performance and reducing the importance of the initial pole set specification. This is achieved by replacing the high-frequency asymptotic requirement of the VF scaling function with a more relaxed condition. Calculated results demonstrate a major improvement of performance when fitting responses that are contaminated with noise. The procedure is also shown to be advantageous for wideband modeling of transmission lines, network equivalents, and transformers. Copyright IEEE

Kategori

Vitenskapelig artikkel

Språk

Engelsk

Forfatter(e)

Institusjon(er)

  • SINTEF Energi AS / Energisystemer

År

2006

Publisert i

IEEE Transactions on Power Delivery

ISSN

0885-8977

Årgang

21

Hefte nr.

3

Side(r)

1587 - 1592

Vis denne publikasjonen hos Cristin