Til hovedinnhold
Norsk English

Multi ejector and the impact of ejector design on the operation of a CO2 refrigeration system

Sammendrag

An ejector with a certain design will have the best performance within a certain area of the operational
envelope. Maximizing the benefit of the ejector can be achieved in two ways; by varying either the design of
the ejector; or change the operational conditions to a point within the desired operation envelope of the
available ejector design. If the design does not suit the current operation point, the ejector will have different
characteristics and reduced efficiency. Different system designs will have different requirements and will
require/benefit most from ejector designs that are adapted to the unique characteristics of each system type.
The present paper is briefly describing an investigation of the impact of the design parameters on the
functionality of the ejector, the capacity control and the system performance. An emphasis was given on the
variation of the motive nozzle of an ejector with fixed geometry. Experimental studies were conducted by
SINTEF with a multi ejector. A steady state model was utilized to study the system implications.

Kategori

Vitenskapelig Kapittel/Artikkel/Konferanseartikkel

Oppdragsgiver

  • Research Council of Norway (RCN) / 244009

Språk

Engelsk

Forfatter(e)

Institusjon(er)

  • Danmark
  • SINTEF Energi AS / Termisk energi

År

2015

Forlag

International Institute of Refrigeration

Bok

Ammonia and CO2 Refrigeration Technologies - Ohrid, Macedonia April 16-18, 2015 - Proceedings

Hefte nr.

2015-2

ISBN

978-2-36215-008-1

Vis denne publikasjonen hos Cristin