Til hovedinnhold
Norsk English

Eliminating Measurement Cable Effects From Transformer Admittance Measurements

Sammendrag

Admittance frequency-sweep measurements is an accepted procedure for characterizing transformer terminal behavior for the purpose of frequency-dependent black-box modeling. The errors introduced by the measurement cables is with one existing practice mitigated by removal of the associated shunt capacitance effect. In this paper, it is shown that the accuracy can be greatly improved by using transmission-line representation of the measurement cables with parameters obtained from standard cable data or from S-parameter measurements. The procedure is demonstrated for the modeling of a 45 MVA generator step-up transformer requiring cable lengths of six meters and an upper frequency limit of 10 MHz.
Les publikasjonen

Kategori

Vitenskapelig artikkel

Språk

Engelsk

Forfatter(e)

Institusjon(er)

  • SINTEF Energi AS / Energisystemer

År

2016

Publisert i

IEEE Transactions on Power Delivery

ISSN

0885-8977

Årgang

31

Hefte nr.

4

Side(r)

1609 - 1617

Vis denne publikasjonen hos Cristin