Switching capability
SATS offers a full range of switching tests and test facilites can be tailored to the client's need in terms of power, voltage and breaking requirements.
HV Direct test
  • 3-phase 4000 MVA short-circuit power;
  • 250 kV, 280 kA peak current, 16 - 60 Hz
MV direct test
  • 3-phase: 250 MVA, 3.6 - 38 kV,
  • 105 kA peak current, 40 kArms 50 Hz
LV direct test
  • 250 MVA, 250 - 1000 V.
  • 100 kA (1 sec),  50 Hz
Synthetic tests
  • Two circuits, 4-parameter TRV, 3.2 MJ,
  • ±660 kV. ac. recovery voltage, 550 kV full-pole tests